A fuse is an electronic protective component whose job is to protect the circuit and prevent damage to electronic equipment and injury to people. A compliant fuse must open the circuit by itself when a fault occurs, and must show no unsafe condition at any moment after the fuse element has melted. A fuse's maximum safe breaking current is also called its rated breaking capacity, which international standards define as the maximum current a current fuse can safely interrupt at its rated voltage load.
Breaking capacity has little bearing on a fuse's protective or current-carrying function, but it is critical to the fuse's safety function. When selecting a fuse type and rating, one rule applies: the rated breaking capacity must be equal to or greater than the maximum short-circuit current of the protected circuit.
Limiting the fuse's own temperature rise caused by the current passing through it keeps the fuse safe in normal operation; a rated voltage equal to or higher than the circuit voltage guarantees dielectric withstand after the fuse opens; and because interruption is the point of greatest energy release, only a sufficient breaking capacity ensures that no unsafe condition appears while that energy is released, which makes the entire interruption absolutely safe.
In practice, when the short-circuit current exceeds a fuse's rated breaking capacity, re-conduction, sustained arcing, ignition and burning, fuse explosion and flying debris can occur, and in severe cases injury to people. (Related reading: How good are Joincircuit fuses, and where are they used?)
The international standard issued by the International Electrotechnical Commission (IEC 60127-1, Miniature fuses - Definitions and general requirements) sets out a number of conditions for testing a fuse's breaking capacity, all of them aimed at safeguarding this vital safety parameter: rated AC supply, with source impedance below 10% of total circuit impedance; closing at 30 electrical degrees after the voltage zero crossing; recovery voltage of 1 to 1.05 times rated voltage held for 30 seconds after interruption; insulation resistance of at least 0.1 MΩ after the test; and none of the unsafe conditions described above at any point in the process.

SMD fuse
Because circuits are classified by supply, breaking capacity is also quoted as two separate figures, AC and DC, and DC duty is normally the more severe of the two. Some fuses are rated for both AC and DC, in which case the AC and DC breaking capacities must be listed separately. Typical breaking capacities of standard-compliant fuses are as follows:
Blade fuses: 50 A, 35 A, or 10 times rated current, whichever is greater.
SMD fuses: 100 A AC, 50 A DC, 35 A, or 10 times rated current, whichever is greater.
These figures show that breaking capacity is not directly related to a fuse's performance, yet it is closely tied to circuit safety. For engineers, breaking capacity must be taken into account when overall circuit safety is assessed; it is an important part of total circuit protection. (Recommended reading: Why do fuses blow? What makes a fuse open, and which factors are involved?)