深圳市集电通实业有限公司

电话 : 0755-8830-8258

邮编 : 518129

邮箱 : andyzheng@jdtfuse.com

网址 : http://www.joincircuit.com/

Gas Discharge Tube Selection Guide

A gas discharge tube is a switching-type protective device that works by gas discharge, and it is used practically wherever overvoltage occurs. To use one well, you have to pick the right device for the actual circuit by reference to its ratings; otherwise the result is worse than no protection at all. The following points need attention during design and use:
 
 
1. Nominal DC breakdown voltage: it must not be lower than 1.5 times the working voltage. Where the current capacity is large enough, a lower DC breakdown voltage can be chosen so that protection takes effect quickly when a surge arrives.
 
 
2. Capacitance should be as small as possible, especially on high-speed signal lines. A GDT used on signals normally has a capacitance below 3 pF; too much capacitance will attenuate the signal. (Related reading: How a Gas Discharge Tube Works and Its Main Parameters)
 
 
3. Consider the effect of residual voltage on the downstream circuit. A GDT cannot be used on a power supply on its own: it has a follow-on (arc) voltage of roughly 30 V or less, and if the working voltage exceeds that value the GDT will stay conducting. It must be used together with a varistor; see the standard circuit.
 
 
4. Current capacity: the surge current rating is set by the required standard level.
 
 
That is part of our gas discharge tube selection guide. If anything remains unclear, leave us a message on our Contact Us page and we will reply as soon as possible. (Recommended reading: What Is the Difference Between Two-Stage and Three-Stage Gas Discharge Tube Protection)