Gas discharge tubes include two-electrode and three-electrode types, with a voltage range from 75 V to 3500 V and over one hundred specifications, and are manufactured, monitored and managed strictly in accordance with CITEL standards. Discharge tubes are commonly used as the first or first two stages of multi-stage protection circuits, where they discharge lightning transient overcurrents and limit overvoltages.
Gas discharge tubes are also easy to find in everyday life, the most familiar example being the surge arrester on street lamps and antennas. They are often simply called surge arresters. The tube is a sealed ceramic package containing two or more metal electrodes separated by a gap, together with an inert gas such as argon or neon. (Related reading: 5KA three-electrode ceramic gas discharge tube, 6*8.5 series surge arrester JTA36G)
How a gas discharge tube works: under normal conditions the tube is in a high-impedance state. When the voltage applied across the electrodes reaches the breakdown level of the gas inside the tube, the tube begins to discharge and changes from high impedance to low impedance, so the voltage across the electrodes does not exceed the breakdown voltage. This keeps the whole circuit safe.

Gas discharge tube
Gas discharge tube main parameters: response time, power capacity, capacitance, DC sparkover voltage, temperature range and insulation resistance. Each of these is explained below.
Response time: the interval from the moment the applied voltage exceeds the breakdown voltage to the moment breakdown occurs, usually on the order of nanoseconds. Power capacity: the maximum energy the tube can dissipate and withstand, normally defined as the current it can carry and dissipate under a fixed 8×20µs waveform. Capacitance: the capacitance between the two electrodes measured at 1 MHz, typically ≤1 pF. DC sparkover voltage: the voltage at which the tube sparks over when the applied voltage rises at a rate of 500 V/s. Temperature range: typically −55 °C to +125 °C. Insulation resistance: the resistance measured across the tube with 50 V or 100 V applied, typically >1010 Ω.