Understanding the Rated Voltage and Rated Current of a Fuse

How should the rated voltage and rated current of a fuse be understood? As commonly defined, the rated voltage is the voltage at which an appliance operates normally, and the rated current is the current it draws at that voltage while running at rated power. The following explains the rated voltage and rated current of fuses in more detail.
 
 
Whether a fuse opens depends mainly on the magnitude of the current flowing through it, not on the working voltage of the circuit. The rated voltage of a fuse is specified from the point of view of safe use: it is the highest working voltage of the circuit at which the fuse can operate safely. (Related reading: What Factors Affect the Service Life of a Fuse)
 
 
A fuse may therefore only be installed in a circuit whose working voltage is lower than or equal to its rated voltage, and only then can it work effectively and safely. Otherwise, when the fuse opens, a sustained arc may occur or the fuse may be broken down by the voltage, endangering the circuit and creating other unsafe conditions.
 
 
The rated current of a fuse is in fact a standardised way of naming a specification. How much current flows through a fuse and at what point it opens are pinned down by choosing one uniform benchmark among the standards, and that benchmark is the rated current. Product standards for fuses lay down detailed rules on current levels and opening times, and because the standards differ, the opening time of a fuse differs as well.
 
 
A fuse has an "opening ratio" whose value is greater than "1" (typically between 1.1 and 1.5); it is the ratio of the fuse’s “conventional non-fusing current” to its “rated current”. It follows that even when the current through the fuse is above the rated current but below or equal to the conventional non-fusing current, the fuse will not open. Fuses also have time-delay behaviour and do not necessarily open immediately (TT, T and F time-delay characteristics).
 
 
For example, with a rated current of 2 A, a current above 2 A does not mean the fuse opens at once; it also depends on the time-delay test result. When buying fuses, therefore, make sure you understand the specification, the standard and the meaning of each parameter. At present fuses are divided into UL (US) and VDE (European) standards. (Recommended reading: Application of Resettable Fuses in Lithium Batteries)
 
 
The points above explain how to understand the rated voltage and rated current of a fuse. If anything is still unclear, feel free to email us and we will reply as soon as possible.