Most engineers have come across fuses at some point, yet some of the industry terminology still causes confusion. The terms below are explained one by one.
Voltage rating: the voltage rating of a fuse is the value compared against the voltage present in the circuit, and it must be equal to or higher than the circuit voltage to keep the circuit safe. For this reason, surface-mount fuses are available in voltage ratings of 24 V, 32 V, 48 V, 63 V and 125 V.
Ambient temperature: a fuse is a temperature-sensitive component. Its current-carrying capability is characterized at an ambient temperature of 25 °C. The higher the ambient temperature, the higher the operating temperature of the fuse, and the lower its current-carrying capability and the shorter its service life. Conversely, the lower the ambient temperature, the longer the fuse lasts.
Normal operating current: at 25 °C the rated current of a fuse should generally be derated by about 25 % to avoid nuisance tripping. Most fuse materials have a relatively low melting temperature, which makes fuses sensitive to changes in ambient temperature. For example, at 25 °C ambient a fuse rated 1 A will usually not work reliably in a circuit whose steady-state current exceeds 0.75 A. (Related reading: how to select a surface-mount fuse)

Rated breaking capacity, also called interrupting capacity: the maximum current that a fuse can reliably interrupt at its rated voltage. During a short circuit a fuse is subjected to repeated transient overload currents far above the normal operating current. Safe operation requires the fuse to remain physically intact, with no bursting or cracking.
Resistance: fuses rated below 1 A can have an internal resistance of a few tenths of an ohm, which has to be taken into account when a fuse is used in a low-voltage circuit. Most fuses are made of positive temperature coefficient materials, so a distinction is drawn between cold resistance and hot resistance. In other applications this parameter is less critical.
Nominal melting energy: the energy required to melt the fuse element, expressed as I2t and read as “ampere-squared seconds”. Accredited certification bodies normally carry out a melting-energy test: a current step is applied to the fuse and the time to melting is measured; if no melting occurs within roughly 0.008 s or more, the pulse current is increased. The test is repeated until the fuse melts within 0.008 s. The purpose is to ensure that the heat generated has no time to escape from the element by conduction, in other words that all of the energy goes into melting the fuse.
In short, when you select a surface-mount fuse, take the normal operating current, the fault current, the I2t value, the ambient temperature, the internal resistance and the rating derating into account. If anything is still unclear, feel free to ask our online sales staff or call us to request samples. (Recommended reading:why a surface-mount fuse sometimes shows high resistance without opening)