Fuse Theory Explained with Practical Examples

Earlier articles set out the theory of fuses; here we work through concrete examples of how that theory applies. Recall that Ir = In × K, where Ir is the working current, In the rated current of the fuse and K the temperature derating factor. The formula makes it clear that the permitted working current becomes steadily smaller as the temperature rises.

 
Temperature derating factor K
 
To make this easier to follow, two examples are given below. Suppose a 20 A time-lag fuse is chosen for a location at 23°C; the maximum working current in the circuit then equals the fuse rating, 20 A (at 23°C). At an ambient temperature of 70°C the derating factor is 80%, so the maximum working current becomes 20 A × 80% = 16 A (at 70°C). (Related reading: How ambient temperature affects fuse performance)
 
 
When selecting a fuse in practice, therefore, the rating alone is not enough: the conditions in which the fuse will be used must be considered as well, and environmental factors matter a great deal.
 
 
Repeated testing by our engineers has shown that the differences between the laboratory environment and real use lie mainly in the mounting cavity, contact resistance, air flow, pulse currents and wiring.


Pulse factor, mounting cavity, contact resistance
 
 