F and T Cartridge Fuses: What's the Difference
In an earlier article we explained the difference between a fuse and a cartridge fuse and gave a brief introduction to selection, but some readers still have a slightly mistaken idea of cartridge fuse part numbers and ask: what is the difference between an F cartridge fuse and a T cartridge fuse? Today we will explain the difference between the two briefly.
fuse, that is, a cartridge fuse, is an electrical component installed in a circuit to keep the circuit operating safely. Other names are used for it, and IEC 127 defines it as a “fuse element”. The names differ but the meaning is the same. Fuses and cartridge fuses are used ever more widely and have been developed in a great many designs; different industries place different requirements on fuses, which has produced varieties that differ in shape, size, mounting style, material, construction, rating and application (conventional tubular fuses, miniature fuses, SMD fuses, automotive fuses and industrial fuses).
Cartridge fuses usually come in fast-acting and time-lag versions, marked T and F respectively: T for time lag and F for fast acting. Alongside T and F there is also breaking capacity, where L generally stands for low breaking capacity, M for medium breaking capacity, H for high breaking capacity and R for very high breaking capacity (current-limiting).
So what is the difference between an F cartridge fuse and a T cartridge fuse? A fast-acting fuse is mostly used on circuit boards or in special equipment: as soon as the current exceeds its rated value it melts instantly, so it can provide short-circuit protection only. A time-lag fuse provides both short-circuit and overload protection, and the larger the current the faster it melts, with no specified time figure. Take a time-lag fuse as an example: with a 10 A fuse and a load current of 30 A it blows within a few seconds, whereas with a load current of 12 A it takes several minutes to blow. In electrical engineering this behaviour is called the "inverse time" characteristic. (Recommended reading: The Evolution of Fuses and Their Technical Requirements)
That is a brief explanation of the difference between F cartridge fuses and T cartridge fuses. If anything is still unclear, please leave a message for us on the Contact Us page and we will reply as soon as possible.