Hold current 0.75A. Maximum voltage 60V. SM package. For overcurrent protection of 48V power modules and low-current loads. Post-trip resistance 1.0Ω. Breaking capacity 10A. Automatic recovery after fault removal.
| Parameter | Value |
| Hold current | 0.75 A |
| Trip current | 1.5 A |
| Maximum voltage | 60 V |
| Maximum fault current | 10 A |
| Initial resistance | 0.23 Ω |
| Post-trip max resistance | 1 Ω |
| Trip current / time | — A / — s |
| Dissipated power | 1.7 W |
| Package | SM package |
| Model | Vmax | R1max | Package | Note |
| MF-SM075 | 30 V | 1 Ω | SM package |
The 60 after the slash is the voltage rating, not a revision. The same-current MF-SM075 is rated 30V and breaks 80A; this part is rated 60V and breaks only 10A. Short-circuit current on a 24V supply is often above 30A, and the excess cannot be broken, so the arc burns until upstream protection acts. A higher-voltage part solves breakdown but trades away breaking capacity. Read both numbers together.
Fresh resistance is 0.23Ω for 0.17V. After reset the limit is 1.0Ω, or 0.75V at 0.75A. On a 48V system this 0.75V is 1.6 percent and downstream design needs no change. Move it to a 5V auxiliary supply and 0.75V takes 15 percent, so chips reset easily.
In the SM series the 0.75A step pairs 60V only with 10A breaking capacity. If 60V is needed and short-circuit current is a concern, drop to the 0.50A step and use MF-SM050, which breaks 40A. If the load truly needs 0.75A, add a fuse stage in the circuit.